Electrical guide to the home distribution board
The terms electricians explain to customers, the rules in DK, DE, CZ and SK, and two quick calculators.
Current from power
How many amps an appliance or circuit draws.
Current: 10 A
On three phases this is the current in each phase with a balanced load. It is not a breaker recommendation.
Voltage drop on a cable
Whether a cable is enough for the length and current.
Voltage drop: 3.13 %
Over 3 % for lighting, within 5 % for other circuits.
After HD 60364-5-52 annex G, conductor at operating temperature, reactance left out.
Breakers B, C and D
- B (3–5 × In)
- Ordinary socket and lighting circuits. A B16 trips instantly at about 48 to 80 A.
- C (5–10 × In)
- Loads with a high inrush, such as motors or many LED drivers at once.
- D (10–20 × In)
- Transformers and large motors. Not “better”, it just trips later.
- What the letter does not say
- The curve does not say how much the circuit may carry continuously, nor which cable it needs.
RCDs and RCBOs
- 30 mA
- The rated residual current. Socket circuits up to 32 A must be behind an RCD of at most 30 mA.
- Type AC, A, F, B
- AC sees alternating residual current only, A also pulsating DC, F also mixed frequencies from inverters, B also smooth DC (EV chargers, solar).
- RCBO
- A breaker and an RCD in one device for one circuit. A fault switches off only that circuit.
- Surge protection
- Type 1+2 at the origin of a house, type 2 in a flat. It does not protect against short circuits or shock.
Earthing systems TN-C, TN-S, TN-C-S and TT
- TN-C
- Protective and neutral conductor share one PEN conductor.
- TN-S
- PE and N run separately through the whole installation.
- TN-C-S
- The PEN splits into PE and N at one point, usually the main board. After the split they never join again.
- TT
- The protective conductor has its own earth electrode; without an RCD the protection can rarely be met.
Phases, poles and sizing
- Single and three phase
- The number of phases of the supply. 3 × 25 A means 25 A in each phase, not 75 A in one.
- 1P, 3P, 4P
- The number of poles of a device. A three-phase board also feeds single-phase circuits spread over L1, L2 and L3.
- Ib ≤ In ≤ Iz
- Design current ≤ breaker rating ≤ cable capacity. Iz depends on installation method, temperature and grouping.
- 1.5 mm² = B10?
- Not always. Installation method, length (voltage drop) and loop impedance decide.
What differs from country to country
The basis is the same (HD 60364); national standards go further in places. Bidmio checks these rules in the board's circuit list.
| Country | 30 mA RCD | RCD type AC | Surge protection | Circuit list |
|---|---|---|---|---|
| Denmark (Stærkstrømsbekendtgørelsen) | every circuit of a dwelling | not used | after a risk assessment | gruppefortegnelse |
| Germany (DIN VDE 0100) | sockets and lighting in dwellings | not used | required in new and extended installations | Stromkreisliste |
| Czechia (ČSN 33 2000) | socket circuits up to 32 A | allowed | after a risk assessment | seznam obvodů |
| Slovakia (STN 33 2000) | socket circuits up to 32 A | allowed | after a risk assessment | zoznam okruhov |
A summary from public sources that electricians from each country are still checking. A project follows the standard in force.
Circuit list, inspection and invoice in one program
Bidmio checks RCDs and circuits under your country's rules, calculates voltage drop and loop impedance, and turns the board into an inspection report and an invoice.
Try the circuit schedule on 3 consumer units free, no card needed. Every feature works on them.
This guide is a learning aid. It does not set the protection, cable sizes or wiring of a particular building; a qualified electrician designs and verifies those.